Transient recovery voltage (TRV) is the high-frequency voltage that appears across a circuit breaker’s contacts right after it interrupts current. It arises when trapped charges on the source and load networks redistribute, lasts only microseconds, and can be several times the system voltage. If it rises faster than the medium regains insulation, the arc reignites or restrikes.

When a fault occurs in a power system, the circuit breaker must interrupt the current and open its contacts. That action creates a high-frequency voltage across those contacts. It can damage the breaker’s insulation and make the arc restrike.
This article explains what TRV is, why it appears, and what it can do to a breaker, and why it is so important in breaker design.
Why Does TRV Appear When a Circuit Breaker Opens?
TRV appears because a circuit breaker is the link between two electrical networks, and opening it breaks that link.
On one side of the breaker is the source-side network, which delivers power: a generating station, a substation, and transmission lines. On the other side is the load-side network, which consumes power: distribution substations, distribution lines, and consumers. The breaker joins them.

When a fault occurs and the breaker opens, the two networks are disconnected from each other. Charge is trapped in each network, and it tries to redistribute. As a result, each network develops a voltage that appears across its own terminal of the interrupter. Call these E1 and E2. Their algebraic sum is the transient recovery voltage.
What Are the Characteristics of TRV?
TRV is a high-frequency voltage that can be several times the normal system voltage, and it lasts only a few microseconds.
High frequency, high magnitude: it can be several times higher than the system voltage.
Oscillating: the waveform typically shows several oscillations.
Very short: it lasts for a few microseconds. After that, the normal power frequency voltage is established.

The shape of the waveform depends on several factors:
The conditions at which the contacts separate.
The type of fault.
The characteristics of the network connected to the breaker.
The switching arrangement used.
TRV is generally greater across the first pole to clear the fault.
How Does TRV Affect a Circuit Breaker?
TRV can make the arc reignite or restrike, which can leave the breaker unable to clear the fault.
When a breaker interrupts a fault, an arc forms in the interrupting medium. The medium is trying to regain its insulating properties, and for the interruption to succeed, it must withstand the fast-rising recovery voltage. In effect, there is a race in the medium between going from a conducting state to an insulating state and the rising TRV.

The medium wins: if the speed at which the medium gains dielectric strength is greater than the rate of rise of recovery voltage (RRRV), the interruption succeeds.
The TRV wins: if the RRRV is greater than that speed, the breaker fails to clear the fault, and the fault current keeps flowing through the arc.
The same race explains how a vacuum breaker can fail. See Why Does a Vacuum Circuit Breaker Fail?
What is Reignition?
Reignition is when current is re-established almost immediately after current zero, because the arc plasma still contains conducting ions.
What is Restrike?
Restrike is a dielectric breakdown that occurs some time after the current has been interrupted.
If TRV is very high, it stresses the medium after it has returned to its insulating state. If the field across the contacts is high enough, the dielectric breaks down, the medium becomes conducting, and current flows again. This generally occurs about half a cycle after the interruption.
Restrike is a very dangerous situation. It can damage the circuit breaker completely, along with other equipment in the substation.
Aspect | Reignition | Restrike |
When it occurs | Almost immediately after current zero | Generally about half a cycle after interruption |
Cause | Arc plasma with conducting ions re-establishes current | Dielectric breakdown of the medium under high TRV |
Result | Fault current continues through the arc | Medium becomes conducting, can damage the breaker and other equipment |
How Do Standards Handle TRV?
Standards such as IEC and ANSI define the TRV conditions and values that a breaker must be tested against to prove its capability.

A breaker that passes all the tests at the conditions defined by the standards is considered capable of handling the different TRVs that different faults can produce. This testing is part of the design-validation process described in type test vs routine test.
Why Does TRV Matter in Circuit Breaker Design?
TRV matters in breaker design because the breaker must be capable of handling high TRV and still clear the fault, so designers must account for it from the start.
A breaker that cannot withstand TRV risks reignition or restrike, which keeps the fault running and can damage the system. That is why the standards test for it, and why considering TRV is of paramount importance in design. The interrupting medium is a large part of the answer. For what is inside two common types, see SF6 circuit breaker components and components of a vacuum circuit breaker.
FAQ
What is transient recovery voltage?
It is the voltage that appears across the contacts of a circuit breaker after the current is interrupted. It is high-frequency and can be several times the normal system voltage.
Why does TRV appear when a breaker opens?
Opening the breaker breaks the link between the source-side and load-side networks. The trapped charges in each network redistribute, and the voltages across the interrupter terminals add up as the TRV.
How long does TRV last?
Only a few microseconds. After that, the normal power frequency voltage is established.
What is the difference between reignition and restrike?
Reignition happens almost immediately after current zero, when the arc plasma still has conducting ions. Restrike happens later, about half a cycle after interruption, when a dielectric breakdown makes the medium conduct again.
How do manufacturers prove a breaker can handle TRV?
They test it to the TRV conditions and values defined in standards such as IEC and ANSI. A breaker that passes all those tests is considered capable of handling the TRVs that different faults can cause.
Conclusion
Transient recovery voltage is the short, high-frequency voltage that appears across a breaker’s contacts after it interrupts current, caused by the trapped charges of the source and load networks redistributing. It lasts only microseconds, but it can be several times the system voltage, and if it rises faster than the interrupting medium regains its insulating strength, the result is reignition or restrike. That is why standards test for it, and why it sits at the centre of circuit breaker design.
To see TRV explained with the network diagram and waveform, watch my complete video on the TheElectricalGuy YouTube channel.
Watch the Youtube Video