Copper loss is the I²R heat in a transformer’s windings and rises with the square of load current. Iron loss, also called core loss, is hysteresis and eddy current heat in the core and stays fixed whenever the transformer is energised, even at no load. Distribution transformers are designed for low iron loss, power transformers for low copper loss.
Imagine a transformer with no load connected. There is no output current, and yet the transformer is warm. If there is no load, where is that heat coming from? And why does the same transformer get much hotter the moment you start loading it?

The answer lies in two different losses, one fixed and one that follows the load. This article explains both, and why they decide which application a transformer suits.
Where Does the Heat in a Transformer Come From?
The heat comes from losses: the small difference between the power going into a transformer and the power coming out.
Take a 10 MVA transformer. You expect almost 10 MVA out, but the output is always slightly less. That difference is loss, and it always appears as heat. It affects efficiency, and every electrical machine has it.

Think of a water pipe with a small leak. You pour in 100 litres and get 98 out. The 2 litres did not vanish. They leaked on the way. In a transformer, that gap heats the core, the winding, and the oil.
The heat comes from two places:
The core: magnetic losses from hysteresis and eddy currents.
The winding: copper losses from the resistance of the wire.
These two families behave very differently, which is the key to this article.
What is Iron Loss in a Transformer?
Iron loss, also called core loss, is the heat produced in the core by the alternating magnetic flux. It exists even when no load is connected.
The moment you energise a transformer, the core sees alternating flux. At 50 Hz, the flux builds, collapses, and reverses 50 times every second. So the core is working even when the load current is zero. That is why iron loss is also called no-load loss: it does not wait for a load. For more on how the core, winding, and insulation work together, see 4 Power Transformer Systems Every Engineer Should Know.
Iron loss has two parts: hysteresis loss and eddy current loss.
What is Hysteresis Loss?
Hysteresis loss is the energy lost as the core is magnetised and demagnetised in each cycle.
The core material is made of tiny magnetic domains. Every half cycle, you force them to flip one way, then flip back the other way. Flipping takes energy, and that energy does not come back. It becomes heat.

Think of bending a wire again and again. Bend it straight, then reverse, then straight again, and the wire gets hot at the bend. You are not breaking it, only working it. The core does the same 50 times a second.
Hysteresis loss cannot be made zero, but it can be reduced by using materials that need less energy to reverse their magnetism, for example CRGO steel.
What is Eddy Current Loss?
Eddy current loss is the heat from small circulating currents induced in the core itself.
The core is a conducting material sitting in a changing flux, so small circulating currents start flowing inside the steel. Think of a whirlpool in a river: the main water flows forward, but near a pillar small circles spin and waste energy. These circles in the core are eddy currents, and they heat it from inside.

The solution is to avoid a solid steel block. Instead, the core is built from thin laminations insulated from each other. Thin sheets break the path of the circulating currents, so the circles are smaller, the current is lower, and the heat is less. That is why a transformer core is laminated.
Why is Iron Loss Called a Fixed or Constant Loss?
Iron loss is fixed because it depends on the applied voltage and flux, not on load current.

It occurs around the clock whenever the transformer is energised at rated voltage. Under heavy loading, a very small variation of around 1 to 2% is seen, because a large load creates a voltage drop. Otherwise it stays fixed, which is why it is also called a constant loss.
What Is Copper Loss in a Transformer?
Copper loss is the heat produced in the windings by load current flowing through their resistance, calculated as I²R.

Because the current is squared, small changes in load create large changes in loss:
At half load, the current is half and the loss is one quarter.
At full load, the current is full and the loss is at its maximum.
At 10% overload, the loss rises by about 21%, since 1.1 squared is 1.21.
Think of a thin extension wire feeding a heater. With the heater off, the wire stays cool. Turn the heater on, and the same wire carries current and starts to warm. A transformer winding behaves the same way.

That is why copper loss is called load loss, or variable loss. At no load it is almost zero, and at full load it is at its maximum. It is also why loading discipline matters: a transformer forced to run overloaded does not just get slightly hotter, it gets hotter in square proportion.
What Other Losses Occur in a Transformer?
Two smaller losses also occur in a real transformer: stray loss and dielectric loss.

Stray loss: leakage flux that does not stay in the core cuts the tank wall, clamps, and structure, and creates heat there. It varies with load, like copper loss.
Dielectric loss: a tiny loss in the insulation under AC stress. It is small in power frequency transformers, but it is still there.
How Are Iron Loss and Copper Loss Measured?
Two tests measure them: the open-circuit test gives iron loss, and the short-circuit test gives copper loss.
The open-circuit test is run with the secondary open, so the power drawn is essentially the iron loss. The short-circuit test is run with the winding carrying rated current, so the power drawn is essentially the copper loss.
Copper Loss vs Iron Loss: Quick Comparison
Aspect | Iron Loss | Copper Loss |
Also called | Core loss, no-load loss, constant loss | Load loss, variable loss |
Where it occurs | Core | Windings |
Cause | Hysteresis and eddy currents | I²R heating in winding resistance |
Depends on | Applied voltage and flux, not load current | Load current, squared |
At no load | Present | Almost zero |
At full load | Almost unchanged (about 1 to 2% variation) | Maximum |
Reduced by | CRGO steel and thin insulated laminations | Keeping loading within rating |
Matters most for | Distribution transformers | Power transformers |
Why Do Losses Decide Which Application a Transformer Suits?
A transformer is designed around its loading pattern: low iron loss where it is energised all day at variable load, and low copper loss where it runs near full load.
Distribution transformers are connected to the supply 24/7, but their loading keeps changing as demand varies. Iron loss runs all the time, so they are designed for low iron loss.
Power transformers serve bulk power transmission, where the loading is close to full and mostly constant. Copper loss dominates there, so they are designed for low copper loss.
Using a high-iron-loss design for distribution would waste energy every hour of the year. For a fuller comparison of the two types, see Power Transformer vs Distribution Transformer.
FAQ
Why is a transformer warm even with no load?
Iron loss. The core sees alternating flux whenever the transformer is energised, so hysteresis and eddy current heating occur even when the secondary current is zero.
Why is a transformer core laminated?
To reduce eddy current loss. Thin insulated sheets break the path of the circulating currents, so the currents are smaller and the heat is lower than in a solid block.
Why does copper loss rise so fast when a transformer is overloaded?
Copper loss follows the square of the current. A 10% overload raises the current by 10% but the loss by about 21%.
Which loss stays the same at all loads?
Iron loss. It depends on voltage and flux, not on load, which is why it is called a fixed or constant loss.
Can hysteresis loss be eliminated?
No. Every cycle flips the magnetic domains, and that takes energy. It can be reduced with materials that need less energy to reverse, such as CRGO steel.
Conclusion
Every transformer loses a little power as heat, and that loss comes from two places. Iron loss in the core is fixed: it appears as soon as the transformer is energised and does not change with load.
Copper loss in the windings is variable: it is nearly zero at no load and rises with the square of current. Understanding the difference explains why an idle transformer is warm, why overloading is costly, and why distribution and power transformers are designed differently.
To see the losses explained step by step with the analogies, watch my complete video on the TheElectricalGuy YouTube channel.
Watch the Youtube Video