The first pole to clear factor (kpp) is the ratio of the power frequency voltage across the first pole to interrupt, before the other poles clear, to the voltage across the poles once all three have interrupted. Nameplates typically show 1.3 to 1.5. It tells you how much extra transient recovery voltage the first pole must withstand.
If you have looked at a circuit breaker nameplate, you have seen a parameter called the first pole to clear factor. It is easy to read past, but it says something important about how the breaker behaves when it clears a fault.

This article explains what it means, how to read the values on the nameplate, and how to use it to calculate the transient recovery voltage across a 145 kV breaker.
Why Do the Three Poles of a Circuit Breaker Open at Different Times?
The three poles open at different times because the three phases are displaced by 120 degrees, and a breaker interrupts at current zero.
In a three-phase system, the phases reach zero 120 degrees apart. A circuit breaker opens at a current zero, when the contacts separate. So each pole interrupts when its own phase current reaches zero, and the poles do not all open at the same time.

Say the first pole opens at one instant. A while later the second opens, and a while after that the third opens. While the first pole has opened, the other two are still closed. That sequence is the source of the problem.
What Happens When the First Pole Clears?
When the first pole clears, a transient recovery voltage appears across its contacts, and it is higher than the TRV across the other two poles.
Take a three-phase symmetrical fault and follow the waveform. The blue phase clears first, and the moment it opens, a transient recovery voltage appears across that pole's contacts. The red and green poles are still closed at this point.

A little later the red phase clears, and a TRV appears across its contacts. Then the green phase clears, and a TRV appears across its contacts too.

It has been studied and observed that the first pole to open faces a higher TRV than the other two. The calculation is given in the relevant IEC standard. For the basics of what TRV is, see What is Transient Recovery Voltage in a Circuit Breaker?.
What Is the First Pole to Clear Factor?
The first pole to clear factor is the ratio between two power frequency voltages: the voltage across the first pole to interrupt, and the voltage across the poles after all three have interrupted.
The formal definition is the ratio of the power frequency voltage across the first interrupting pole, before current interruption in the other poles, to the power frequency voltage across the pole or poles after interruption in all three poles.
Split it into two values:
Value 1: the power frequency voltage across the first interrupting pole, while the other two are still closed. Which pole is first depends on the instant the fault occurs. It could be R, Y, or B.
Value 2: the power frequency voltage across the poles after interruption in all three phases.
The first pole to clear factor is value 1 divided by value 2.
What Do Values Like 1.3 and 1.5 Mean?
A value of 1.3 means the first pole to clear must sustain 1.3 times the power frequency voltage that appears across the poles when all three have cleared.
If the ratio were 1, the TRV across the first pole would be the same as across the other poles. Nameplates, however, show values from 1.3 to 1.5. These are not random numbers. They come from calculations in the IEC standard, which defines the factor by rating and by fault type. For example, the factor for a terminal fault is different from the factor for an out-of-phase condition.
How Do You Calculate TRV Using the First Pole to Clear Factor?
You calculate the TRV peak with an IEC formula that combines the rated voltage, the first pole to clear factor, and an amplitude factor.
The formula is:
You calculate the TRV with an IEC formula that combines the rated voltage, the first pole to clear factor, and an amplitude factor.
uc = (Ur × kpp × √2 × kaf) / √3
uc: the TRV that appears across the first pole.
Ur: the rated voltage.
kpp: the first pole to clear factor.
kaf: the amplitude factor, defined by the IEC.
What is the Worked Example for a 145 kV Breaker?
For a 145 kV breaker with a terminal fault, the TRV across the first pole comes to about 215.47 kV.
Input | Value |
Rated voltage (Ur) | 145 kV |
First pole to clear factor (kpp), terminal fault | 1.3 |
Amplitude factor (kaf) | 1.4 |
Putting the values in: (145 × 1.3 × √2 × 1.4) / √3 = 215.47 kV.
This is the TRV that appears across the first pole to open after a fault. It is higher than the power frequency voltage across all three open poles, and the breaker must be able to sustain it. Remember that these factors are for a terminal fault, and the IEC gives different values for other fault conditions.
Why Must All Three Poles Withstand the Higher TRV?
All three poles must withstand it because nobody knows in advance which pole will open first.

Which pole clears first depends on the instant at which the fault occurs. It could be the R phase, the Y phase, or the B phase. So the manufacturer must make sure that every pole can sustain the higher TRV. When a nameplate shows a first pole to clear factor of 1.3 or 1.5, it indicates that the breaker can take this higher TRV without any problem.
What Happens If a Breaker Does Not Meet the Requirement?
A breaker that does not meet the requirement may restrike, which keeps the fault running and can harm the whole system.
If the breaker is not confirmed for the first pole to clear factor, the arc can restrike during a fault. The manufacturer must make sure the breaker complies with the IEC standards, and the proof is type testing, in which the breaker is shown to withstand this higher TRV. See type test vs routine test for how type testing works.
FAQ
What is the first pole to clear factor?
It is the ratio of the power frequency voltage across the first pole to interrupt, before the other poles clear, to the power frequency voltage across the poles after all three have interrupted.
Why do the poles of a breaker clear at different times?
The three phases are 120 degrees apart, and a breaker interrupts at current zero. Each pole therefore interrupts when its own phase reaches zero, at a different instant.
What does a first pole to clear factor of 1.3 mean?
The first pole to clear must sustain 1.3 times the power frequency voltage that appears across the poles after all three have cleared.
Why do nameplates show values between 1.3 and 1.5?
The IEC standard calculates them, and defines them by rating and fault type. For example, the value for a terminal fault differs from the value for an out-of-phase condition.
How do you check that a breaker can handle the higher TRV?
Through type testing, where the manufacturer proves the breaker can withstand the TRV defined by the IEC standards. A breaker with a first pole to clear factor on its nameplate has been shown to handle it.
Conclusion
Because the three phases are 120 degrees apart, a breaker's poles interrupt at different times, and the first pole to clear faces a higher transient recovery voltage than the others. The first pole to clear factor, typically 1.3 to 1.5 on the nameplate, expresses exactly how much higher.
It feeds into the TRV calculation, which for a 145 kV breaker with a terminal fault gives about 215.47 kV. Since any pole could clear first, every pole must withstand it, and type testing is how the manufacturer proves it.
To see the waveforms and the worked example on screen, watch my complete video on the TheElectricalGuy YouTube channel.
Watch the Youtube Video

About Author
Gaurav Joshi
Gaurav started his career on the floor of the electrical industry — not in a classroom. Working across Siemens and Schneider Electric, he saw firsthand how wide the gap was between what colleges teach and what the industry actually needs.
So he did something about it.
Today, he's built a global community of 300,000+ engineers and professionals across YouTube and beyond — and TheElectricalGuy Academy is where that knowledge lives in its most structured, practical form.